The RE 316SH-2Lconventional detectors are designed to work with all conventional Panels. These detectors are low profile and have O dual LED?s for 360 visual indication. The blinking LED?s indicate normal operating conditions whereas the steady state indicate fire status. RE 316SH-2L is a fixed cum rate of rise heat detector using a thermistor. These detectors will raise an alarm when the detector O reaches 59 C(Fixed) or when the change in temperature exceeds O the rate of rise of 11 C / min.
Multi Detectors
Ravel RE 316SH – 2L Conventional Multi Detector
- UL Approved
- Dual LED’s for 360 visibility
- Advanced detection and communication protocol
- Easy installation and maintenance
- Sleek low-profile housing design
- Regular 100mm base
65.00 AED 74.75 AED
SKU: 100688
Category:
Brand: Ravel
Operating Voltage: | 9 ~ 33V DC |
Reset Voltage: | less than 1V |
Standby Current: | 50 micrA. |
Start up Time: | 60s |
Start up Current: | 170 ?A. |
Alarm Current: | 90 mA (Max) |
Remote Output: | 15 mA maximum open collector |
Thermal Rating: | 59 C (138 F) |
Rate of Raise of Temperature: | 11.1 C / min (20 F/min) |
Smoke Sensitivity: | (1.9 ? 0.76) % / ft |
Air Velocity: | 0 – 4000 fpm |
Operating Temperature: | 10 C to 37.8 C |
Storage Temperature: | -10 C to 60 C |
Humidity | 0 – 95% RH, non-condensing: |